Delta Ultron Series HPH Integrated battery 40kVA 380/400/415V, 50/60Hz, inbuilt battery 2×40 – GES403HH33A035
KSh2,950,000 Original price was: KSh2,950,000.KSh2,555,000Current price is: KSh2,555,000. Exc. VAT
- Rated Power (kW): 40 kW
- Phase Configuration: Single-phase input, single-phase output
- Input Voltage Range: 305-478 VAC
- Frequency (Input): 50/60Hz ± 10% (auto-sensing)
- Power Factor (Input): > 0.99 (at full load)
- Current Harmonic Distortion Factor: < 3%
- Battery Type: Sealed Lead-Acid or Lithium-Ion (configurable)
- Battery Voltage: 240 VDC
Delta Ultron Series HPH Integrated battery 40kVA 380/400/415V, 50/60Hz, inbuilt battery 2×40 – GES403HH33A035
The Delta ULTRON series HPH 40 kW UPS (GES403HH33A035) is a high-capacity uninterruptible power supply system designed to provide dependable power protection for critical applications. With its advanced features and battery backup, this UPS ensures a continuous and clean power supply to safeguard mission-critical equipment and sensitive loads.
With a power capacity of 40 kW, the ULTRON series HPH UPS is designed for single-phase input and single-phase output, making it suitable for a wide range of applications
Product Specifications
Execution | floor |
Purpose | for data centers |
Number of phases (input-output) | 3-3 |
GENERAL CHARACTERISTICS | |
Rated power, kVA | 40 kVA |
Active power, kW | 40 kW |
ENTRANCE | |
Rated voltage | 380/220, 400/230, 415/240 Vac. current |
Voltage range | – 20% ~ 20% (full load), – 40% ~ 20% (70% load) |
Current harmonic distortion factor | < 3% |
Power factor | > 0.99 (at full load) |
Frequency | 40~70Hz |
EXIT | |
Voltage | 380/220, 400/230, 415/240 Vac. current |
Voltage harmonic distortion factor | < 1.5% (linear load) |
Voltage regulation limits | ± 1% |
Frequency | 50/60Hz ±0.05Hz |
Overload capacity | <105%: continuous operation 106% ~ 125%: shutdown after 10 min. 126% ~ 150%: shutdown after 1 min. >150%: shutdown after 1 s |
ACCUMULATOR BATTERY | |
Battery Type | Supports maintenance-free/valve-regulated lead-acid/cylindrical/nickel-cadmium batteries |
Nominal battery life | 9.5 min.(At 70% load with internal batteries.) |
Charge current | 9A |
COMMUNICATION INTERFACES | |
Standard | 1 SMART slot, 1 MINI slot, 2 parallel ports, 1 RS232 port, 1 REPO port, 1 charger detection port, 2 dry contact inputs, 6 dry contact outputs |
EFFICIENCY | |
Normal mode (on-line) | up to 96% (UPS efficiency of HPH 40-120K models tested by TÜV) |
OTHER | |
Parallel redundancy and expansion | Yes, parallel connection of up to 4 UPSs with a total power of up to 480 kW |
Remote control | up to 99% |
Emergency power outage | Yes (local and remote) |
Manual bypass switch | Yes |
TERMS OF USE | |
Working temperature | 0~40˚C |
Relative humidity | 5~95%(no condensation) |
Noise level | < 60 dB |
DIMENSIONS AND WEIGHT | |
UPS Dimensions | 490 x 830 x 1400 mm |
UPS Weight | 365 kg |
COMPLIANCE | |
Safety and EMC | CE, RCM |
Visit the Delta store Kenya for a more extensive variety of Delta UPS at incredibly affordable pricing. In order to give you peace of mind with every transaction, we are one of the reputable Delta dealers in Kenya and offer limited manufacturer warranty for selected Delta products. For the most affordable Delta supplier offers, visit our website right now to learn about our inventory and get in
Brand
Delta
Be the first to review “Delta Ultron Series HPH Integrated battery 40kVA 380/400/415V, 50/60Hz, inbuilt battery 2×40 – GES403HH33A035” Cancel reply
You must be logged in to post a review.