Description
Ups Delta rt-Series 8kVA S w/ 20x9Ah batt. & Pdb (UPS802R2RT0B035)
The Delta RT-Series 8kVA is a double-conversion, rack/tower-mountable UPS system that offers advanced power protection and management features. It is suitable for various applications, including data centers, server rooms, telecommunications equipment, and other critical loads.
Product Specifications
Input Parameters:
- Rated Power (VA/W): 8000 / 8000
- Voltage Range: 100~280V (single phase, 2 wires plus ground)
- Voltage Range (Linear Derating):
- Frequency: 40~70Hz
- Power Factor: > 0.99 (at full load)
- Current Harmonic Distortion Factor: < 3%
- Input Connections: Input Terminal Block x 1
Output Parameters:
- Power Factor: 1
- Voltage: 200, 208, 220, 230, 240 VAC (single phase)
- Frequency: 50/60Hz ± 0.05Hz
- Voltage THD: < 2% (with linear load)
- Overload Capacity:
- ≤ 105%: continuous operation
- 106 ~ 125%: 5 min
- 126 ~ 150%: 1 min
- Output Connections:
- IEC C13 x 6 (non-managed)
- IEC C19 x 4 (non-managed)
- Terminal Block x 1 (non-managed)
- IEC C19 x 1 (managed)
Efficiency:
- Normal Mode: Up to 95.5%
- Economy Mode: Up to 99%
Rechargeable Batteries:
- Battery Capacity: 20×9 Ah
- Battery Voltage: 240 V DC (current)
- Charging Current:
- 1.5 A (default)
- 8 A (maximum)
Common Parameters:
- Noise Level: 50 dB
- Display: Graphic LCD display with multilingual interface
- Communication Interfaces:
- 1 MINI slot
- 1 USB port
- 1 RS232 port
- 1 RS485 port
- 1 REPO/ROO port
- 4 dry contacts
- Dimensions (W × D × H), mm: 440×750×218
- Weight, kg: 85.5
- Ambient Operating Temperature: 0~55°C
- Relative Humidity of the Environment: 5 ~ 95% (non-condensing)
UPS Runtime Table (Delta RT-Series 8kVA S w/ 20x9Ah batt. & PDB):
- The UPS runtime is provided for different loads and the number of batteries:
- Number of Batteries \ Load %:
- 25% Load
- 50% Load
- 75% Load
- 100% Load
- UPS + 1 VBM:
- 36.3 min
- 15.6 min
- 9.3 min
- 5.1 min
- UPS + 2 VBM:
- 71 min
- 27 min
- 14.5 min
- 9.6 min
- UPS + 3 VBM:
- 119 min
- 49.5 min
- 27.5 min
- 17.5 min
- UPS + 4 VBM:
- 167.5 min
- 73.5 min
- 42.5 min
- 27.5 min
- UPS + 5 VBM:
- 217 min
- 98 min
- 58 min
- 39 min